| SERIES | PTI15 | |||||
| PRESSURE RANGES |
15psiv | -14.5 psig to 0 psig | 50psig | 0 psig to 50 psig | 10psia | 0 psia to 10 psia |
| 15psic | -14.5 psig to 15 psig | 100psig | 0 psig to 100 psig | 15psia | 0 psia to 15 psia | |
| 30psic | -14.5 psig to 30 psig | 160psig | 0 psig to 160 psig | 25psia | 0 psia to 25 psia | |
| 50psic | -14.5 psig to 50 psig | 200psig | 0 psig to 200 psig | 30psia | 0 psia to 30 psia | |
| 100psic | -14.5 psig to 100 psig | 300psig | 0 psig to 300 psig | 50psia | 0 psia to 50 psia | |
| 160psic | -14.5 psig to 160 psig | 500psig | 0 psig to 500 psig | 100psia | 0 psia to 100 psia | |
| 200psic | -14.5 psig to 200 psig | 1000psig | 0 psig to 1,000 psig | 160psia | 0 psia to 160 psia | |
| 300psic | -14.5 psig to 300 psig | 1500psig | 0 psig to 1,500 psig | 200psia | 0 psia to 200 psia | |
| 10psig | 0 psig to 10 psig | 2000psig | 0 psig to 2,000 psig | 300psia | 0 psia to 300 psia | |
| 15psig | 0 psig to 15 psig | 3000psig | 0 psig to 3,000 psig | |||
| 25psig | 0 psig to 25 psig | 5000psig | 0 psig to 5,000 psig | |||
| 30psig | 0 psig to 30 psig | 7500psig | 0 psig to 7,500 psig | |||
| psiv = vacuum gauge pressure psic = compound gauge pressure psig = gauge pressure psia = absolute pressure Other ranges available on request |
||||||
| ACCURACY | 1 | ±0.5% (of span, non-linearity, BFSL per IEC 61298-2 at reference conditions) | ||||
| SWITCH-OUTPUT | 1 | 2 N.O. or N.C. (PNP or NPN) | 5 | 2 N.O. or N.C. switch (PNP/NPN) with 0 Vdc to 10 Vdc* | ||
| 2 | 1 N.O. or N.C. (PNP or NPN) with 4 mA to 20 mA |
6 | 1 N.O. or N.C. switch (PNP/NPN) with 4 mA to 20 mA/0 Vdc to 10 Vdc ** |
|||
| 3 | 1 N.O. or N.C. (PNP or NPN) with 0 Vdc to 10 Vdc |
7 | 2 N.O. or N.C. switch (PNP/NPN) with 4 mA to 20 mA/0 Vdc to 10 Vdc *, ** |
|||
| 4 | 2 N.O. or N.C. (PNP or NPN) with 4 mA to 20 mA* |
|||||
| PROCESS CONNECTIONS |
2 | 1/4" NPT male | 10 | G1/4B EN837 | 83 | G 1/2 B male EN837 |
| 8 | 1/2" NPT male | 45 | 7/16-20 SAE J514 FIG 34B (Non-Adjustable) |
|||
| ELECTRICAL CONNECTIONS |
25 | M12 x 1 (4-pin) | 48 | M12 x 1 (5-pin) | ||
| OPTIONS | IOL | With IO-Link | ST8 | Threaded Orifice (0.8 mm) | ||
* Available only with a M12x 1 (5-pin) connector
**Can switch between 4mA to 20 mA / 0 Vdc to 10 Vdc
If you are viewing on a smaller screen or with screen zoom, please use the horizontal scroll bar at the bottom of this table to see all information.
| SPECIFICATIONS | |
| Pressure ranges | Compound and standard ranges from 0 psig to 10 psig through 0 psig to 7,500 psig |
| Switching parameters Number Function Contact rating Response time Accuracy Switch point Hysteresis |
Individually adjustable via external control keys 1 or 2 (PNP or NPN) N.O., N.C., window, hysteresis (freely adjustable) 250 mA max. ≤5 ms ≤ 0.5 % of span .25 to 100% of full scale Fully adjustable |
| Transmitter parameters Output signal Accuracy Non-repeatability Adjustment IO-Link |
4 mA to 20 mA or 0 Vdc to 10 Vdc; programmable and freely adjustable ≤±0.5% of span including non-linearity, hysteresis, zero offset and end value deviation (corresponds to measured error per IEC 61298-2) < 0.1% of span (IEC 61298-2) Freely scalable within the range of 5:1 Version 1.1.4 |
| Service life | 100,000,000 load cycles |
| Temperature ranges | Compensated 32 °F to 176 °F (0 °C to 80 °C) Media -4 °F to 185 °F (-20 °C to 85 °C) Ambient -4 °F to 176 °F (-20 °C to 80 °C) Storage -4 °F to 158 °F (-20 °C to 70 °C) |
| Display | 14 segment-LED, red 4-digit, height 0.35” |
| Power requirement* | 15 - 35 Vdc |
| Current consumption | Max. 45 mA for versions without 4-20 mA output signal, Max. 70 mA for versions with 4-20 mA output signal, Total consumtpion max. 600 mA including switching current |
| Proof pressure | 2 times full scale |
| Measuring element | <150 psi: 316L Stainless steel ≥150 psi: 316L, PH grade Stainless steel |
| Housing material | 304 Stainless Steel |
| Connection | 316 Stainless Steel |
| Environmental rating | IP65 and IP67 per IEC 60529 |
| Electromagnetic rating | RFI, EMI and ESD protection |
| Electrical protection | Protected against reverse polarity, over-voltage and short circuit |
| Shock | > 50 g’s according to IEC 60068-2-27 |
| Vibration | > 20 g’s according to IEC 60068-2-6 |
| Weight | Approx. 0.49 lb. |
*Unregulated
NOSHOK offers a wide variety of standard & elevated pressure, and reduced pressure replaceable and non-replaceable diaphragm seals, designed to isolate and/or protect the pressure measuring instrument from corrosive, viscous, contaminated or very high temperature process media.
View NOSHOK's Diaphragm Seal offering
NOSHOK Digital Indicators provide local indication for pressure, level and temperature transmitters.
View NOSHOK's Digital Indicators offering
NOSHOK's Distribution Manifolds connect multiple instruments to one diaphragm seal, eliminating multiple connections that lead to possible leak paths.
View NOSHOK Distribution Manifolds

WARNING: This product can expose you to chemicals including Lead, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

WARNING: This product can expose you to chemicals including Nickel, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

WARNING: This product can expose you to chemicals including Lead, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

WARNING: This product can expose you to chemicals including Nickel, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
The NOSHOK All Non-Metallic Diaphragm Seal & Pressure Transmitter/Switch assembly is ideal for water, wastewater & chemical feed applications.
View NOSHOK All Non-Metallic Diaphragm Seal & Pressure Transmitter/Switch assembly
Steam Syphons Temperature 1/4" NPT vs. Pressure charts
Steam Syphons Temperature 1/2" NPT vs. Pressure charts

WARNING: This product can expose you to chemicals including Lead, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

WARNING: This product can expose you to chemicals including Nickel, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

WARNING: This product can expose you to chemicals including Nickel, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

WARNING:This product can expose you to chemicals including Lead and Nickel, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
A: In many industrial applications, the terms pressure transmitter, pressure transducer and pressure sensor are used interchangeably. Traditionally, a transmitter referred to an instrument with a current output signal such as 4 mA to 20 mA, and a transducer referred to an instrument with a voltage output signal such as 0 Vdc to 10 Vdc. Today, all three terms are commonly used to describe electronic pressure measurement devices, so a NOSHOK pressure transmitter or transducer is often considered a type of pressure sensor.
A: When these terms originated there was a distinctive difference between the two. A transmitter was referred to as an instrument with a current signal, for example 4 mA to 20 mA, and a transducer was referred to as an instrument with a voltage signal, for example 0 Vdc to 10 Vdc. As time has progressed these terms are now commonly interchanged for reference to either output signal.
A: Proof pressure, which is higher than the full scale pressure point, is the limit that you can go to without affecting the performance and calibration of the transducer. The burst pressure, on the other hand, is the limit that you can go to before there is pressure chamber rupture and damage. An overload limit specification used sometimes means that proof and burst ratings are identical.
A: Radio Frequency Interference (RFI) and Electromagnetic Interference (EMI) refer to the effects electrical noise can have on instruments. RFI frequently comes from hand held walkie-talkies and EMI comes from AC motors in the vicinity of the instrument. ESD, or Electrostatic Discharge, comes from many sources including the application itself. CE compliant transmitters and transducers incorporate protection techniques and components to minimize most of the interference.
A: Most diaphragm seals can be used with pressure transducers and transmitters. The key is to assemble and fill the seal properly, being careful not to entrap air in the fill fluid.
A: The steam syphon is necessary in steam pressure applications. It is important to isolate the transmitter sensing diaphragm from the high temperature encountered with steam pressure applications.
A: As with other pressure measurement instruments including gauges, pressure pulsations and spikes are issues with pressure transmitters. Whenever the pressure of an incompressible fluid is measured, there is the potential for pulsations and spikes, which can damage pressure transmitters. An orifice installed in the pressure connection by NOSHOK can protect the transmitter from damage. Where there is the possibility of clogging the small orifice, an attachable piston snubber is recommended.
A: All pressure measurements are inherently differential in theory. Gauge pressure is referenced to ambient atmospheric pressure, and absolute pressure is referenced to a vacuum contained in an evacuated chamber within the transmitter. The level measurement is also a differential measurement, with its reference to ambient atmospheric pressure. In order for the submersible level measurement to be referenced to atmospheric, the cable contains a vent tube which runs the complete length of the cable and vents to atmospheric pressure at the junction box connection, which is out of the liquid.
A: The transmitter measures the hydrostatic pressure produced by the liquid level higher than the point where the instrument is located. The higher the liquid, the higher the pressure.
A: Voltage output transducers are available with a fourth connection which is electrically the same as the power supply common to connect to wiring configurations that require it.
A: A smaller diaphragm is less easily damaged, and positioning the sensors directly behind the diaphragm minimizes fill fluid and enables active temperature compensation directly at the point of measurement.
A: A turndown ratio, also commonly known as rangeability, refers to the ratio between the full-scale range and the minimum point of measure, indicating the range in which an instrument can accurately measure the media. For example, if a pressure transmitter has a maximum calibration range of 0 to 300 psi and a turndown ratio of 10:1, the span can be adjusted anywhere between 0 to 30 psi and 0 to 300 psi. The higher the turndown ratio, the higher the rangeability, which can also help minimize required inventory.
More questions? Contact NOSHOK Customer Support at info@noshok.com